          • FLN36 Indoor AC SF6 Load Break Switch

          FLN36 Indoor AC SF6 Load Break Switch

          FL(R)N36 Indoor AC High Voltage SF6 Load Break Switch and LBS-Fuse Combination are used for the three-phase AC 50/60Hz RMU and terminal power station. The switches are suitable for protecting the 10kV, 24kV and 35kV power system's on load situation. The switch can switch off the on load current, closed loop current, no load transformer capacity and cable charging current. The switch with fuse combination can cut off any current, when the current is in the range of the rated short-circuit breaking current. They are suitable for the RMU, combined transformer, etc..

          Technical Information

          Technical Specification

           

           

           

           

          Rated voltage

          kV

          12

          24

          40.5

          Rated current

          A

          630

          630

          630

          Rated power frequency

          Hz

          50/60

          50/60

          50/60

          Short circuit making capacity

          kA Peak.

          62.5

          50

          50

          Peak withstand current

          kA Peak.

          62.5

          50

          50

          Short time current

          kA eff.

           

           

           

          1Sec.

           

          25

           

           

          2Sec.

           

           

          20

          20

          Max. breaking capacity in co-operation with fuses IEC 62271-105 (IEC 420 1990-11)

          A

          1530

          920

          630

          Mainly active load breaking capacity

          A

          630

          630

          630

          Cable charging current

          A

          630

          630

          630

          Power frequency withstand voltage 50Hz 1 min,:

           

           

           

           

          - To earth and between poles

          kV

          42

          55

          95

          - Across isolating distance

          kV

          45

          70

          120

          Impulse withstand voltage 1.2/50μ s:

           

           

           

           

          - To earth and between poles

          kV

          75

          125

          190

          - Across isolating distance

          kV

          85

          145

          220

          Mechanism Endurance

          cycles

          1000

          1000

          1000


          Overall and installation dimensions